INSTALLATION INSTRUCTIONS For HUD Code Wind Zone 1, or IBC 2009,90 mph, Exposure CVersion 12/9/2009INDEX PAGESECTION NUMBERINTRODUCTION 2G
Page 10 4/3/2013Example of a Single Section 14' x 72' H om e WIND ZONE I for Single Section Homes Using V ector Dynamics Foundation S
Page 11 4/3/2013Example of a Double Section 28' x 72' HomeWIND ZONE I for Double Section HomesUsing Vector Dynamics Foundation SystemsS
Page 12 4/3/2013Example of a Triple Section 32' x 72' HomeWIND ZONE I for Triple Section HomesUsing Vector Dynamics Foundation SystemsSo
Page 13 4/3/2013Example of a Double Section 28' x 72' HomeWIND ZONE I for Double Section Homes (High Pier Sets)Using Vector Dynamics Fou
Page 14 4/3/2013For metal piers, place the piers in the center of the Vector pads. Set the single 4x4 or two 2x4’s through the piers, and bumps
Page15 4/3/2013VECTOR DYNAMICS INSTALLATION DESIGN INSTRUCTIONSVectorDynamicFoundationSystemsmaybeusedonlyonhomessetonsoilscl
Page16 4/3/2013Vector Dynamics Systemfor Concrete ApplicationsInstructionsThese instructions are an addendum to the standard Vector Dynamics
Page 17 4/3/20139. Putawasherandnutononeofthe3/8”x3-3/4”wedgeanchors.Thenutshouldbescrewedon enough to have 1 or 2 threads
Page18 4/3/2013Asphalt InstallationTheseAsphaltinstructionsareanaddendumtothestandardVectorDynamicsconcreteinstructions.Readan
TIE DOWN ENGINEERING • 255 Villanova Drive SW • Atlanta, GA 30336www.tiedown.com (404) 344-0000 Fax (404) 349-0401
Page 2 4/3/2013TIE DOWN ENGINEERINGVECTOR DYNAMICS INSTALLATION DESIGN INSTRUCTIONSIntroductionThese instructions describe the proper use of the
Page 3 4/3/2013GENERAL INSTALLATION INSTRUCTIONSSITE PREPARATIONIt is necessary that the home site be properly graded and sloped to prevent wate
Page 4 4/3/2013Vector DynamicsFoundation SystemsComponent Parts ListVector System 2000Part#59018Single piece pads with strapsand slo
Page5 4/3/2013Vector 2000 3 Sq. Ft. PadPart#592711requiredwith59026LongitudinalSystem2requiredwith59024LateralSystemLon
Longitudinal Stabilizer DevicesAs an alternate to installing longitudinal anchors and stabilizer plates, the installer may use longitudinal stabilizin
Page 7 4/3/201350 in.max.Figure 150 in.max.24”26” MaximumUnequal Pier HeightsHomeswithunequalpierheightsarelimitedto50”ma
Page8 4/3/2013080707,D973UnitWidthMax.PierHeightMax.SidewallHeightMax. Unit Length forNumber of Vector Systems 2 3 4 5 6136 32&qu
ABDCLong U-BoltsPage 9 4/3/2013Set-Up Instructions forVector System #590181. Set Vector PadsClear all vegetation where pads will rest